Recent controlled testing on operating HVAC equipment demonstrated AirSenz’s ability to detect monitored fault conditions, alert technicians and recognize recovery. Watch a clogged filter, an electrical anomaly and low refrigerant through the complete sequence.

THE FULL DEMONSTRATION7:54 · Narrated by Bobby Ferrel
Actual test readings. Monitoring alerts. Recovery confirmation.Download video
Read narration

Three faults. Three clear signals. This AirSenz test follows a clogged filter, added electrical load, and low refrigerant, from normal operation through detection and verified recovery.

The test system pairs a Goodman heat pump and air handler, using blower tap three and R thirty-two refrigerant. Outdoor temperature is seventy-five degrees Fahrenheit.

We begin at eleven twenty A M, before the filter restriction. One-minute detail shows the critical changes, with faster transitions between the key events.

First, a healthy qualified cycle. Static pressure is stable, and the air handler draws just under two and a half amps. This is our reference before the restriction.

With the filter restricted, return static pressure climbs well above the commissioned baseline. The change is clear in the running readings.

The filter restriction also increases air-handler current by about eleven percent. This comparison uses qualified readings from the healthy and restricted runs.

At eleven fifty-one, AirSenz detects the filter restriction. The completed cycle is about forty percent above the static-pressure baseline.

After the restriction is removed, running static pressure returns to its healthy range. AirSenz evaluates the next qualified cycle to confirm recovery.

The portal marks the symptom cleared at twelve eleven. At twelve twelve, the engine records the filter alert as resolved, following the healthy qualified cycle.

Next, the electrical test. An Ohmite resistive load bank adds one amp, followed by a second amp, for a total added load of two amps.

Before that added load, the normal qualified cycle shows outdoor current just under seven amps. This establishes the healthy reference.

The first higher reading appears at twelve fifty-seven. Outdoor current rises to nearly eight amps.

Two minutes later, the second step takes current to just under nine amps. Both load additions are now visible.

At one oh four, AirSenz detects sustained excess current. The detection result is about one hundred thirty percent of baseline, above the one hundred twenty percent threshold.

The alert remains active through shutdown. During the next cooling run, current returns near baseline, and qualified operation supplies the recovery evidence.

At one twenty-eight, the electrical alert resolves after a healthy adjacent qualified cycle. The record now shows both the anomaly and its recovery.

The third test tracks low refrigerant through subcooling and the air temperature differential. The subcooling baseline is about fifteen degrees.

A normal qualified cooling cycle comes first. The difference between return and supply air temperature is about twenty-four degrees. This is our healthy reference.

At two fifty-five, the operator removes one pound of refrigerant. The next sustained cooling cycle reveals the change.

With low charge, subcooling stays around nine to ten degrees. The air temperature split also falls, from about twenty-four to twenty-one degrees. That is a drop of almost three degrees during qualified operation.

At three thirty-five, AirSenz detects low subcooling and identifies low charge as the likely cause. The detection cycle is about thirty-six percent below baseline.

At three fifty, the operator restores the pound of refrigerant. The readings that follow show the air temperature split back near normal, around twenty-four to twenty-five degrees. Subcooling continues recovering.

At five oh two, the symptom moves to improving. The following cooling run provides another qualified cycle for the recovery check.

The next qualified cycle verifies that the recovery holds.

The air temperature differential tells the same story. About twenty-four degrees before the test, about twenty-one with low charge, and back near twenty-five during recovery. Cooling performance has returned to its normal range.

At five twenty-eight, the refrigerant alert resolves. Clearing-cycle subcooling is back to about fifteen degrees. All three test alerts are now resolved.

The recorded event history connects each detected fault with its verified resolution. That is a complete service story, from the first signal to the recovery.

For homeowners, better system performance means more comfort and less wasted energy. Catch small issues early to help lower operating costs and prevent avoidable breakdowns. Sometimes the answer is simple: change a filter, or clear a drain line, and avoid an unnecessary service call.

Put more money back in your household budget. Better efficiency and one avoided emergency service call could save around five hundred dollars a year. Earlier insight helps you turn small corrections into lasting value.

Help your system go the distance. AirSenz protected systems pair earlier insight with proactive maintenance and timely repairs, helping homeowners work toward up to twenty years of dependable comfort. Catch small issues sooner. Protect your investment. Get more from the system you already own.

For HVAC contractors, faster diagnosis can create room for more revenue. Save twenty-five minutes on site, and a technician handling four calls could fit a fifth into the same field day. One more customer served, without adding another technician. Arrive informed, focus the repair, and verify the result.

Improve first-visit repair success with a clearer diagnosis and the right parts. Catch and correct installation errors before completing the job, then confirm healthy performance after the repair. Fewer callbacks mean more productive visits, stronger customer confidence, and more time for revenue-producing work.

For utilities, corrected faults can translate into meaningful energy savings. A representative heat-pump home could save around a thousand kilowatt-hours a year, rising to fifteen hundred in our stronger correction example. Across a thousand similar homes, that is roughly one to one and a half million kilowatt-hours a year. Focus outreach, correct waste, and follow performance after repairs.

For multifamily owners, give your apartment maintenance team HVAC insight before they walk through the door. Guide routine checks, prepare the right parts, and know when to bring in a specialist. Earlier repairs help extend equipment life and reduce repeat visits. Faster resolutions protect tenant comfort and satisfaction. Across the property, use system condition and service history to prioritize capital spending. Coordinate visits with residents and schedule work before an urgent complaint becomes an after-hours emergency.

Industry research shows why these conditions matter. Department of Energy guidance connects clean filters with lower cooling energy use. NIST modeling shows the energy penalty of undercharge, while Berkeley Lab documents savings from fault detection and diagnostics.

See what earlier insight can do for your home, your service business, your multifamily property, or your utility program. Visit AirSenz dot A I to request a demo. Know more. Sooner.

An AirSenz milestone

From detecting HVAC faults to confirming recovery.

After 19 years in the HVAC business, we know that identifying a problem is only part of the job. Technicians need useful information to investigate it and a way to check the monitored conditions after corrective work.

What we observed

During recent testing on operating HVAC equipment, AirSenz detected fault conditions, sent alerts and provided readings to guide the technician’s investigation. As the test conditions were corrected, AirSenz used the equipment’s readings to recognize that the monitored faults had cleared.

Recovery recognized automatically

No one had to manually tell AirSenz that the monitored fault was resolved. The operating data supplied the evidence for clearing the alert. This gives the service team a record of both the condition that needed attention and its recovery.

These tests mark an important step forward for our team at Intellicair. We are continuing to validate AirSenz across equipment and operating conditions as we work toward more informed, proactive HVAC service.

Follow the evidence

Watch the complete sequence.

01 / CHANGE
A test condition is introduced.Compare the changing readings with normal operation.
02 / DETECTION
AirSenz raises an alert.The alert and readings help guide a technician’s investigation.
03 / RECOVERY
AirSenz recognizes recovery.After correction, the readings show when the monitored condition has cleared.

Explore each test.

Go straight to the fault you want to see.

TEST 01 · 3:31

Clogged filter

Watch how a filter restriction changed the operating readings during our recent testing—and see recovery after airflow was restored.

What to watch: Static pressure, indoor current and the fault-to-clear sequence.

Download video
Read narration

One restricted filter. A clear signal. This AirSenz test follows normal airflow, filter restriction, detection, and verified recovery. Watch how pressure and indoor current tell the story.

The test system pairs a Goodman heat pump and air handler, using blower tap three and R thirty-two refrigerant. Outdoor temperature is seventy-five degrees Fahrenheit.

These are the actual lab photographs. On the left, the inlet is restricted for the filter test. On the right, the inlet is unobstructed. The operating readings show what changes when airflow is restored.

We begin at eleven twenty A M, before the filter restriction. One-minute detail shows the critical changes, with faster transitions between the key events.

First, a healthy qualified cycle. Static pressure is stable, and the air handler draws just under two and a half amps. This is our reference before the restriction.

With the filter restricted, return static pressure climbs well above the commissioned baseline. The change is clear in the running readings.

The filter restriction also increases air-handler current by about eleven percent. This comparison uses qualified readings from the healthy and restricted runs.

At eleven fifty-one, AirSenz detects the filter restriction. The completed cycle is about forty percent above the static-pressure baseline.

After the restriction is removed, running static pressure returns to its healthy range. AirSenz evaluates the next qualified cycle to confirm recovery.

The portal marks the symptom cleared at twelve eleven. At twelve twelve, the engine records the filter alert as resolved, following the healthy qualified cycle.

Here is the actual portal cycle record. The restricted cycle meets the alert rule. The following healthy cycle falls back below the threshold, and the portal marks the symptom cleared at twelve eleven.

The M C P screenshot shows the filter alert and its resolution together. Detection is recorded at eleven fifty-one. At twelve twelve, the prediction engine resolves the alert after a healthy qualified cycle.

A small filter change can deliver real value. For homeowners, early notice can turn a comfort complaint into a simple maintenance task, with less wasted energy and fewer unnecessary calls. Contractors and property teams can focus on the right action sooner. For utilities, correcting restricted airflow supports more efficient system operation.

Put more money back in your household budget. Better efficiency and one avoided emergency service call could save around five hundred dollars a year. Earlier insight helps you turn small corrections into lasting value.

Help your system go the distance. AirSenz protected systems pair earlier insight with proactive maintenance and timely repairs, helping homeowners work toward up to twenty years of dependable comfort. Catch small issues sooner. Protect your investment. Get more from the system you already own.

See how AirSenz can turn early warning into confident action. Visit AirSenz dot A I to request a demo. Know more. Sooner.

TEST 02 · 3:12

Electrical anomaly

Follow two steps of added electrical load, the detected anomaly and the return to normal current.

What to watch: Outdoor current, the alert and resolution after the added load is removed.

Download video
Read narration

Two load steps. One clear signal. This AirSenz test follows an increase in electrical load during our recent testing, from normal operation through detection and verified recovery.

The test system pairs a Goodman heat pump and air handler, using blower tap three and R thirty-two refrigerant. Outdoor temperature is seventy-five degrees Fahrenheit.

An Ohmite resistive load bank adds one amp, followed by a second amp, for a total added load of two amps. A healthy cooling cycle comes first.

Before that added load, the normal qualified cycle shows outdoor current just under seven amps. This establishes the healthy reference.

The first higher reading appears at twelve fifty-seven. Outdoor current rises to nearly eight amps.

Two minutes later, the second step takes current to just under nine amps. Both load additions are now visible.

At one oh four, AirSenz detects sustained excess current. The detection result is about one hundred thirty percent of baseline, above the one hundred twenty percent threshold.

The alert remains active through shutdown. During the next cooling run, current returns near baseline, and qualified operation supplies the recovery evidence.

At one twenty-eight, the electrical alert resolves after a healthy adjacent qualified cycle. The record now shows both the anomaly and its recovery.

The actual portal alert history records both electrical decisions. The excess-current condition is confirmed at one oh four, then cleared at one twenty-eight. These are the system records behind the replay.

This is the original M C P alert. It identifies sustained excess electrical consumption and records the prediction engine as resolving it. The green resolution message confirms healthy operation in the recovery cycle.

Spot the change. Focus the diagnosis. An excess-current alert gives a qualified technician a clearer starting point, helping address a developing issue before it becomes a larger repair. Homeowners gain earlier insight. Contractors can arrive better prepared, and property teams can prioritize service. Utilities can use confirmed corrections to target avoidable energy waste.

Put more money back in your household budget. Better efficiency and one avoided emergency service call could save around five hundred dollars a year. Earlier insight helps you turn small corrections into lasting value.

Help your system go the distance. AirSenz protected systems pair earlier insight with proactive maintenance and timely repairs, helping homeowners work toward up to twenty years of dependable comfort. Catch small issues sooner. Protect your investment. Get more from the system you already own.

See how AirSenz can turn early warning into confident action. Visit AirSenz dot A I to request a demo. Know more. Sooner.

TEST 03 · 4:04

Low refrigerant

See the system response when one pound of refrigerant is removed, then restored.

What to watch: Subcooling, cooling temperature difference and the confirmed recovery.

Download video
Read narration

Less refrigerant. Less cooling. A clear recovery. This AirSenz test follows normal operation, a reduction in refrigerant charge during our recent testing, and restoration of healthy performance.

The test system pairs a Goodman heat pump and air handler, using blower tap three and R thirty-two refrigerant. Outdoor temperature is seventy-five degrees Fahrenheit.

This test tracks low refrigerant through subcooling and the air temperature differential. The subcooling baseline is about fifteen degrees.

A normal qualified cooling cycle comes first. The difference between return and supply air temperature is about twenty-four degrees. This is our healthy reference.

At two fifty-five, the operator removes one pound of refrigerant. The next sustained cooling cycle reveals the change.

With low charge, subcooling stays around nine to ten degrees. The air temperature split also falls, from about twenty-four to twenty-one degrees. That is a drop of almost three degrees during qualified operation.

At three thirty-five, AirSenz detects low subcooling and identifies low charge as the likely cause. The detection cycle is about thirty-six percent below baseline.

At three fifty, the operator restores the pound of refrigerant. The readings that follow show the air temperature split back near normal, around twenty-four to twenty-five degrees. Subcooling continues recovering.

At five oh two, the symptom moves to improving. The following cooling run provides another qualified cycle for the recovery check.

The next qualified cycle verifies that the recovery holds.

The air temperature differential tells the same story. About twenty-four degrees before the test, about twenty-one with low charge, and back near twenty-five during recovery. Cooling performance has returned to its normal range.

At five twenty-eight, the refrigerant alert resolves. Clearing-cycle subcooling is back to about fifteen degrees. Qualified operating data confirms the recovery.

The portal captures the actual low-charge test cycle. After startup, the system reaches qualified operation. The completed cycle supplies the evidence for the low-subcooling alert at three thirty-five.

This is the next qualified recovery cycle in the portal. The system holds healthy operation after startup. Its completed readings support clearing the refrigerant symptom, and the record shows the cleared result.

The original M C P screenshot completes the story. It shows the low-subcooling alert, low refrigerant charge as the likely cause, and automatic resolution at five twenty-eight after a healthy qualified cycle.

Restore the charge. Restore comfort. Earlier low-charge insight helps homeowners act before poor cooling turns into a bigger problem. Contractors can arrive ready to check charge and confirm recovery. Property teams can schedule repairs before repeat tenant complaints, while utilities can target energy waste from underperforming equipment.

Put more money back in your household budget. Better efficiency and one avoided emergency service call could save around five hundred dollars a year. Earlier insight helps you turn small corrections into lasting value.

Help your system go the distance. AirSenz protected systems pair earlier insight with proactive maintenance and timely repairs, helping homeowners work toward up to twenty years of dependable comfort. Catch small issues sooner. Protect your investment. Get more from the system you already own.

See how AirSenz can turn early warning into confident action. Visit AirSenz dot A I to request a demo. Know more. Sooner.

What does this mean for you?

The same test evidence, with the context that matters to your role.

These demonstrations of our recent testing use recorded operating data and monitoring screenshots. They show fault detection and recovery under the test conditions and represent a development milestone. We are continuing to validate AirSenz across equipment and operating conditions. Savings and equipment-life examples in the videos are illustrative projections, not measured results of these tests; actual outcomes depend on the system, conditions and corrective action.